UPS KR Series 1~3KVA User’s Manual
10
equipment in equipment rooms with allowed conditions. Refer to Fig. 3-1 for
the precautions of UPS installation and use.
Fig. 3-1 Precautions of UPS Installation and Use
1 Place UPS on flat floor (avoid oblique and ragged floor).
2 Keep good ventilation, the distance of the back and side to the wall should
be above 30cm~50cm, to facilitate heat emission.
3 Avoid placing it in the location with sunniness, rain and dampness.
4 Never place it in the location with corrosive air.
5 Do not place articles on or around the UPS, to prevent the vent hole from
being blocked. No person is allowed to sit on it.
3
33
3.
..
.4
44
4 Selection of Cable
3
33
3.
..
.4
44
4.
..
.1
11
1 Selection of Input Air Switch
Before the input coil in of the equipment, install an air switch or a distribution
box compliant with the power and capability of the equipment, to isolate it with
commercial power. Consider especially the charge power and the current
shock, the input air switch can be higher than 1.5-2 times most current of UPS
Vue de la page 15