UPS KR Series 1~3KVA User’s Manual
-15-
line wire (L), neutral wire (N) and ground wire (GND) is correct. Whether
the connection of AC input wire is firm.
2 Inspection of AC output wire: Whether the AC output wire color
spectrum is normative. Whether the wire size of AC output cable is
suitable. Whether switch in the control switch outside. Whether the
connection of line wire (L), neutral wire (N) and ground wire (GND) is
correct. Whether the connection of AC output wire is firm.
3 Inspection of ground wire: Whether the ground wire of UPS is connected
to the ground line bank of the equipment room. Whether the connection
of ground wire is reliable.
4 The inspection of the voltage difference between neutral wire and
ground wire: the voltage difference should be less than 5Vac.
5 If the customer adopts the configuration of long time-delay model,
examine whether the battery cable connection of main unit box and
battery box is correct and reliable.
6 If the UPS is installed with remote monitoring equipment, examine
whether the connection of relevant RS232 serial port is correct.
7 Examine whether the wiring is in order, whether the cable binding
accord with the technical criterion.
8 Examine whether the installation and wiring are in favor of the future
system modification, expansion and maintenance.